Product Description
Acti 9 C120N, Circuit Breaker, 1P, 100A, C Curve A9N18358
Main
range of product | C120 | |
---|---|---|
range | Acti 9 | |
product name | C120 | |
product or component type | Miniature circuit-breaker | |
device short name | C120N | |
device application | Distribution | |
poles description | 1P | |
number of protected poles | 1 | |
[In] rated current | 100 A at 30 °C | |
network type | AC | |
trip unit technology | Thermal-magnetic | |
curve code | C | |
breaking capacity | 3 kA Icu at 380…415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2 | |
suitability for isolation | Yes conforming to IEC 60947-2 |
Complementary
network frequency | 50/60 Hz | |
---|---|---|
[Ue] rated operational voltage | 380…415 V AC 50/60 Hz | |
magnetic tripping limit | 5…10 x In | |
[Ics] rated service breaking capacity | 15 kA 75 % conforming to EN/IEC 60947-2 – 130 V AC 50/60 Hz | |
limitation class | 3 conforming to EN/IEC 60947-2 | |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 | |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 | |
contact position indicator | Yes | |
control type | Toggle | |
local signalling | ON/OFF indication | |
mounting mode | Clip-on | |
mounting support | 35 mm symmetrical DIN rail | |
comb busbar and distribution block compatibility | NO | |
9 mm pitches | 3 | |
height | 81 mm | |
width | 27 mm | |
depth | 73 mm | |
net weight | 0.205 kg | |
colour | White | |
mechanical durability | 20000 cycles | |
electrical durability | 5000 cycles conforming to IEC 60947-2 | |
connections – terminals | Tunnel type terminals1…50 mm² rigid | |
wire stripping length | 15 mm | |
tightening torque | 3.5 N.m | |
earth-leakage protection | Without |